Charging System - Failure 

Transmitter A1A1 " Charging System - Failure"


Contents

Definition

Theory

Sampling Point(s)

Detection/Threshold Point(s)

Supporting Indications

Conflicting Indications

Supporting Documentation


Definition:

The forward current developed by the A10 charging switch exceeded 175 AMPs or the "ON" drive remained on in excess of 275 micro-seconds.

Theory:

The A10 "Charging Switch" (figure 11-5, sheet 2) supplies current ( 175 Amps max ) to the charging transformer (A7T2) producing a magnetic field.  When the "charging switch" turns off, the magnetic field collapses. The longer the switch is on, the greater the energy stored in the "charging transformer" will be.  The "on" time must not exceed 275 micro-seconds.  The collapsing field induces a charge into the PFN through the A12A5 diode assembly. The collapsing field develops a ring or flyback that is shunted by the "flyback diodes".

Additional charging switch information:
The A10 "Charging Switch" turns on internal transistors upon reception of "MODCHRGTR-" (modulator charge trigger) if the proper enabling signals are true (28VDC from A2K1D, HVONRMPRTN and CHGEN).  The length of time that the transistors are on is controlled by comparing the current sample from A10T4 (top right of figure 11-5, sheet2) and a voltage sample (top left of  figure 11-5, sheet 2) from A1R3 on signal PFNWDREF for wide pulse and A1A2R74 on signal PFNNARREF for narrow pulse.  Selection of reference signal is determined by the signal PFNSHAPER which is a indication of the PFN's switch position.

A10 "Charging Switch" Wave forms

Sampling Point(s):

The forward current is sampled in the A10, "charging switch" by T4.  Top, right of figure 11-5, sheet 2
The time limit is checked by the driving circuits on  the A10A1 board. Top, center of figure 11-5, sheet 2

Detection/Threshold Point(s):

The sample is monitored by the circuits in the A10A1 card inside the charging switch.  See figure11-5 sheet 2, left of center.

Supporting Indications:

The "TIME-OUT FAULT LED" (left of center on figure 11-5, sheet3) should be illuminated when this fault is present.  Remember the fault is no longer detected after a fault reset.

Wave forms measured at A10A1 TP1 and TP2 ( OFF and ON drive) show a on time near 275 micro-seconds.

Comparison of the wave form at TP7 could be compared to a  wave form made earlier (baseline measurments) to determine if there is a substantial change in current.  This would only be of value if your system was measured in good operating condition with a known PFN voltage and no modulator components had been replaced.

Conflicting Indications:

None

Supporting Documentation:

EHB 6-511

Return to Top of Page

Return to Primary Alarm Page

Return to A1A1 Fault Panel



 

Last Updated on October 02, 1998