MODULATOR SWITCH
CONTENTS
-
BACKGROUND
-
SIGNAL SOURCE
-
SIGNAL DESTINATION
-
LIMITS AND FAULTS
BACKGROUND
The Stack Monitor A12A9 (see figure
11-5 sheet 5) monitor the RBDT switch assembly
A12A1 fault status, and sends modulator voltage and current samples
to Control and Monitoring. The Voltage
Equalization board A12A8 (see figure 11-5 sheet 4) sends RBDT voltage
samples to Stack Monitor. The RBDT voltage samples are applied to
a stack of 10 comparators. Each comparator in the summing amplifier
logic examines the voltage across one element of the RBDT stack.
The comparator output are the equivalent of a go/no-go indication for each
element. All 10 outputs are summed together into a voltage summary
signal (SUMVLT). The SUMVLT signal is compared to two thresholds.
If one or two elements fail, SUMVLT drops below the first threshold, and
a stack maintenance signal (MNT) is generated. If three or more elements
fail, SUMVLT drops below the second threshold and a stack fault signal
(FLT) is generated and the MNT signal is cleared.
SIGNAL SOURCE
The signal MODSWMNT originate on the Stack Monitor Board A12A9 and
enter Control and Monitoring at J 26-10 & 30 (see 11-7 sheet 10) of
the Control Card Rack A3. And enter the RMS Interface A3A3 for further
action.
SIGNAL DESTINATION
After entering Control and Monitoring, MODSWMNT is forwarded to
the Fault Bus at Port06EN- as Transmitter Data (TDATA). It also leaves
on bubble 1010-1 as MODSWMNT- for the Fault Display Panel. There
at bubble 1010 MODSWMNT- (see 11-7 sheet 1) goes out to light the lamp
for Maintenance Required Modulation Switch. This fault will not disable
the transmitter.
LIMITS AND FAULTS
If one or two RBDTs fail, SUMVLT drops below the first threshold,
and a stack maintenance signal (MNT) is generated.
Transmitter Start
Main Menu