WAVEGUIDE PRESSURE
CONTENTS
-
BACKGROUND
-
SIGNAL SOURCE
-
SIGNAL DESTINATION
-
LIMITS AND FAULTS
BACKGROUND
The Waveguide Pressurization Unit UD6
supplies dry air for the waveguide and Spectrum filter to decrease chances
for it to arc. It consist of a compressor
and pressure tank with supporting controls and valves. It is
capable of producing very dry air at an output rate of 5 SCIM (Standard
Cubic Inches per Minute) at a pressure of 5 PSIG (Pounds per Square Inch
Gauge). It is a Lightweight unit (58 lbs.) designed for wall mounting
and is used to keep the waveguide components internal dry.
SIGNAL SOURCE
The source of the Waveguide Pressure signal (W/G PRESSURE FAULT)
originates at the Waveguide Pressurization Unit UD6. The signal W/G
PRESSURE FAULT leaves UD6 via Utilities Junction Box 7A1 and continue
on to the Digital Analog Unit (DAU), where it is routed to the Transmitter
UD3 at J3.
SIGNAL DESTINATION
W/G PRESSURE FAULT enter Control and Monitoring at J21-4
on the Control Card Rack A3 as WGPRESSAL (see figure 11-7 sheet 9).
WGPRESSAL then change its name to W/GPRESS as it enter the RMS interface
card A3A3 where it is place on the Fault Bus during Port02EN- as
Transmitter Data (TDATA). At bubble 905-11 W/GPRESS- is used to disable
the transmitter. It also leaves the RMS interface card at bubble
912-1 and goes to the Fault Display Panel A1A1 (see figure 11-7 sheet 1)
at bubble 912 to light the lamp for Waveguide pressure.
LIMITS AND FAULTS
The Waveguide Pressurization unit pressurizes the Spectrum
Filter to 25 psi nominal for the purpose
of ensuring that moist atmospheric air which could cause arcing is excluded
by a positive pressure from the interior of the Spectrum Filter.
The alarm is set when the pressure drop below 20 psi, and will be display
on the Man Machine Interface (MMI) as Spectrum Filter low pressure.
Transmitter Start
Main Menu